FAS linkage intelligent double flaps
Superior wind load resistance and snow load
Seamless corner and superior waterproof
Temperature control release and remote control
Heat insulated aluminum alloy profile
Larger areas of natural skylight, ventilationand smoke exhaust
Intelligent Control System
The smoke vent can open to exhaust smoke automaticallyin case of fire.
Each smoke vent unit can be monitored andcontrolled (showing the status
of open, dose and error feedback).
1) Electric actuator is 24V DC. It has self lock function andlimit switch. Gas springs are
equipped to realize three -point support and make sure its stability.
2) Pneumatic actuator has various emergency open measuressuch as common compressed air,
control box emergencydevice, temperature sense of emergency. It's safe and reliable.Gas springs
are equipped to realize three- point supportand make sure its stability.
Technical Performancesand Strengths
Meet the standard GB15930-2007 <Fire dampersfor building venting and smoke-venting system>
Aluminum alloy profile with seamless corner, which has superior waterproof and corrosion resistantperformance.
Glazing can be replaceable for easy maintaining.
Temperature control release device and remotecontrol to realize intelligent and reliable control.
Wind load resistance: operational certainty of ventsunder wind stress equivalent to 1500 Pa.
Water tightness: GB/T7106-2008 Grade 6
Air tightness: GB/T7106-2008 Grade 8
K value: lower than 2.2 W/(m2.K)Low temperature resistance: -25 C.
High temperature resistance: 300 C 30 mins.
Reliability: 20000 cycles times opening and cosingfor daily ventilation, 1000 cycles times opening andclosing for smoke exhausting.
Snow load: operational certainty of vents undersnow load 500Pa.